Hardware Replacement
7 HardwareReplacement
This section contains instructions on how to replace operator panel hardware.
Only components included in the latest bill of material and spare parts list are
allowed. See Available Spare Parts for iX Panel T40.
7.1 ModeSwitches
The iX Panel T40 has four mode switches (DIP switches) located on the rear side
of the operator panel.
1 2 3 4
ON DIP
1 2 3 4
ON DIP
Warning:
Themodesbelowaretobeusedwithcaution.
Themodeswitcheshavethefollowingfunctions: 1=ON,0=OFF
Each letter in “MODE” has a corresponding mode switch.
MODE Description
0000 “Runmode”-boo tsCE,norm
aloperation.
0010 SystemRestore,reset
sthelesystemandregistry,
reinstallsthesyste
mprogram(OPsys_bxxx.CAB).Restores
theoperatorpanelto
factorysettings.
Warning! Informationcaneasilyaccidentlybelost.
0100 ImageLoadmode(Sysload)allowsupgradingofthe
rmwareintheoperatorpanel.
Note: Allles
includingthelesystemintheoperator
panelwillbed
eletedwhenupgradingwithImageLoader.
1000 ServiceMen
umode,theservicemenuforthesystem
programis
shown. AllowstheusertosetIPconguration,
eraseth
epro ject,calibratethetouchscreenetc. See
section
ServiceMenufordetails.
1100 Notus
ed(runmode).
BeijerElectronics, MAEN004