10.3. AdditionalInformationforULApprovedInstallations
ThedriveisdesignedtomeettheULrequirements.Inordertoensurefullcompliance,thefollowingmustbefullyobserved.
InputPowerSupplyRequirements
SupplyVoltage 200240RMSVoltsfor230Voltratedunits,+/‐10%variationallowed.240VoltRMSMaximum
380480Voltsfor400Voltratedunits,+/‐10%variationallowed,Maximum500VoltsRMS
Imbalance Maximum3%voltagevariationbetweenphasephasevoltagesallowed
AllDriveunitshavephaseimbalancemonitoring.Aphaseimbalanceof>3%willresultinthe drivetripping.Forinput
supplieswhichhavesupplyimbalancegreaterthan3%(typicallytheIndiansub‐continent&partsofAsiaPacific
includingChina)themanufacturerrecommendstheinstallationofinputlinereactors.Alternatively,thedrivescanbe
operatedasasinglephasesupplydrivewith50%derating.
Frequency 5060Hz+/‐5%Variation
ShortCircuitCapacity VoltageRating MinkW(HP) MaxkW(HP) Maximumsupplyshortcircuitcurrent
230V 0.37(0.5) 18.5(25) 5kArms(AC)
230V 22(30) 75(100) 10kArms(AC)
400/460V 0.75(1) 37(50) 5kArms(AC)
400/460V 45(60) 132(200) 10kArms(AC)
400/460V 160(250) 250(350) 18kArms(AC)
Allthedrivesintheabovetablearesuitableforuseonacircuitcapableofdeliveringnotmorethantheabove
specifiedmaximumshortcircuitAmperessymmetricalwiththespecifiedmaximumsupplyvoltage.
Incomingpowersupplyconnectionmustbeaccordingtosection4.3
AllDriveunitsareintendedforindoorinstallationwithincontrolledenvironmentswhichmeettheconditionlimitsshowninsection10.1
Branchcircuitprotectionmustbeinstalledaccordingtotherelevantnationalcodes.Fuseratingsandtypesareshowninsection10.2
SuitablePowerandmotorcablesshouldbeselectedaccordingtothedatashowninsection10.2
Powercableconnectionsand tighteningtorquesareshowninsection3.4
ThedriveprovidesmotoroverloadprotectioninaccordancewiththeNationalElectricalCode(US).
Whereamotorthermistorisnotfitted,ornotutilised,ThermalOverloadMemoryRetentionmustbeenabledbysettingP412=1
Whereamotorthermistorisfittedandconnectedtothedrive,connection
mustbecarriedoutaccordingtotheinformationshownin
section4.7