4.8. ControlTerminalWiring
Allanalogsignalcablesshouldbesuitablyshielded.Twistedpaircablesarerecommended.
PowerandControlSignalcablesshouldberoutedseparatelywherepossible,andmustnotberoutedparalleltoeachother
Signallevelsofdifferentvoltagese.g.24VoltDCand110VoltAC,shouldnot
beroutedinthesamecable.
Maximumcontrolterminaltighteningtorqueis0.5Nm
4.9. ConnectionDiagram
4.9.1. PowerTerminalDesignations
IncomingMainsPowerSupply
For1PhaseSupply,connectto
L1/LandL2/Nterminals.
For3PhaseSupply,connectto
L1,L2&L3terminals.
Phasesequenceisnot
important.
MotorConnections
ConnectthemotortotheU,V&W
terminals.
Themotorearthmustbeconnected
tothedrive
OptionalBrakeResistor&DCBus
Connections
WhereaBrakeresistorisused,it
mustbeconnectedtotheBR+and
DC+terminals
ProtectiveEarth/Ground
connection.
ThedrivemustbeEarthed/
Grounded
4.9.2. ControlTerminalConnections&FactorySettings
Open Closed 
+24VSupply(100mA)/ExternalInput
+24V
1
DigitalInput1 Stop Run(Enable) DIN1
2
DigitalInput2 ForwardRotation ReverseRotation DIN2
3
DigitalInput3 AnalogSpeedRef PresetSpeed DIN3
4
DigitalInputs:8
30VoltDC
+10Volt,10mAOutput
+10V
5
AnalogInput1(Digitalinput4) AIN1
6
0V
7
0V
OutputSpeed
AnalogOutput:010Volt/420mA,20mAMax
8
AOUT1
0VoltSupply/ExternalInput
0V
9
0V
OutputCurrent
AnalogInput2(Digitalinput5) AIN2
10
AnalogOutput:010Volt/420mA,20mAMax
11
AOUT2
ExternalHardwareEnableCicuit
STO+
12
STO‐
13
RelayContacts
250VAC/30VDC
5AMaximum
14
RL1C
DefaultFunction:
Healthy
/Fault
15
RL1NO
16
RL1NC
17
RL2A
DefaultFunction:
Running
18
RL2B
L1/L
L2/N
L3