Additional Installation Tips
6.7 CableandBusTerminationRS485
Use shiel ded and twisted pair cable. The pair c apacitance may not exceed
52.5 pF/m and area at least 0.25 mm
2
(AWG 24), if you want to use the
maximum transfer distance and maximum transfer speed.
0 V, the reference voltage for communication should be includ ed in
the cabling. With two-way communication use two pairs; one pair for
communication and one pair for 0 V.
The shield mus t be grounded at one end. The other end is usually grounded,
but with longer distances or when there is a difference in the ground potential,
theshieldshouldbeconnectedtothegroundvia0.F/250Vplastic
capacitor to prevent ground current in the braided shield. A number of
manufacturers recommend that the shield be grounded at each node. Various
manufacturers have different systems for bus termination.
Depending on the recipients design, the bus wires may be on the same level or
require pull-up or pull-down to ensure that no faulty signals are detected w hen the
bus is in resting mode (all transmitters are disconnected).
6.8 COMPortCommon-ModeVoltage
The COM port I/Os have special restrictions for common-mode voltage with
respect to ground.
COMPort MaximumCommon-ModeVoltageRange
COM1 - RS232 -15 V to+15 V
COM2 - RS422/RS485 -7 V to+7 V
BeijerElectronics, MAEN165
27