Additional Installation Tips
6.6 GalvanicIsolation
Internal electronics
VCC
0 V (GND)
Filter
+24 V DC
0 V
galvanic
isolation
galvanic
isolation
RS422/485 RS422 USB USBUSB
Ethernet
10 nF
The communication ports COM1 and COM2 have built-in galvanic isolation
from the terminal and the input power supply. The communication port grounds
are bonded to protective earth ground and therefore to one another. Both Ethernet
ports have galvanic isolation as well. There is no galvanic isolation between the
terminal and the input power supply. If galvanic isolation is required between the
terminal and the power supply an external isolation device is required.
Caution should be taken when connecting peripherals to the terminal. Many
peripherals including USB devices will bond the terminal’s signal ground (0 V) to
the protective earth ground. Bonding signal ground and protective earth ground
may increase e lectrical emissions and introduce communication errors.
Operator panel
Modular controller
Printer
PC
Different ground potential
= Internal 0 V (GND) connection
PC
galvanic
isolation
RS232RS422/485
USB
USB device
Power CPU COM COM2
=
Note:
It is very important to make sure that the 24 V feedin the external insulation unitis not
connected to one of thecommunication outlets. If it does not have 100% insulation
againstthe 24 V feed,disturbancesand groundingcurrentsfrom the0 Von the24 V
side will disrupt communication.
Using this typeof unitsolves o ne problem but creates alarger problem! A substandard
installationmaywork now, but problemsmayarise when other devicesare connected.
BeijerElectronics, MAEN165