Installation
4.
Connect the cables in the specified order, according to the drawing and steps
below.
Caution:
• EnsurethatthePanelPCandthecontrollersystemhavethesameelectrical
grounding(referencevoltagelevel),otherwiseerrorsincommunicationmay
occur.
• ThePanelPCmustbebroughttoambienttemperaturebeforeitisstartedup. If
condensationforms,ensurethatthePanelPCisdrybeforeconnectingittothe
poweroutlet.
• Ensurethatthevolta geandpolarityofthepowersourceiscorrect.
• Useonlyshieldedcommunicationcables.
• Separatehighvoltagecablesfromsignalandsupplycables.
24V DC
RS422/RS485
24V DC
1
CF CARD
B
A
C
D
RS232
Controller
Power
Ethernet
– Connect cable A.
– Connect cable B, using an M5 screw and a grounding conductor ( as short
as possible) with a cross-section of minimum 2.5 mm
2
.
– Connect cable C.
– Connect cable D .
5.
Carefully remove the laminated film over the Panel PC display, to avoid static
electricity that could damage the panel.
3.2.1 OtherConnection
sandPeripherals
Cables, peripheral equipment and accessories must be suitable for the application
and its environment. For further details or recommendations, please refer to the
supplier.