APPLICATIONNOTEANBEIP2038 Date:15/02/12
ANBEIP2038ModbusRTUControlandRegisterMapping
4
63 Userregister13 03,06 Read/Write
64 Userregister14 03,06 Read/Write
65 Userregister15 03,06 Read/Write
66 Analogoutput1user 03,06 Read/Write
67 Analogoutput2user 03,06 Read/Write
68 Reserved 03,06 Read/Write
69 Reserved 03,06 Read/Write
70 Relayoutput1user 03,06 Read/Write
71 Relayoutput2user 03,06 Read/Write
72 Relayoutput3user 03,06 Read/Write
73 Relayoutput4user 03,06 Read/Write
74 Relayoutput5user 03,06 Read/Write
75 Userdisplayscaling 03,06 Read/Write
76 Userdisplaydecimal 03,06 Read/Write
77 Userspeedreference 03,06 Read/Write
78 Usertorquereference 03,06 Read/Write
79 Userramp 03,06 Read/Write
80 Scopeindex1,2 03,06 Read/Write
ControlandStatusRegisterDescriptions:
Readandwriteregisters
Register1:DriveControlCommandWord
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Highbyte Lowbyte
Bit0: Run/Stopcommand:Setto1toenable(run)thedrive.Setto0todisable(stop)thedrive.
Bit1: Faststoprequest.Whensetto1thedrivewilldeceleratetostopusingthe2
nd
decelerationramp(P225).
Bit2: ResetFaultRequest.Setto1inordertoresetthedrivefollowingatrip/fault.
 (Note:Thisbitmustberesettozerooncethefaultisclearedtopreventunexpectedreset)
Bit3: Coaststoprequest.Setto1
toissueacoaststopcommand.
Fornormaloperation,Bit3hasthehighestpriority,bit0hasthelowestpriority(bit3>bit1>bit0). For example if the control
wordissetto0x0009bythenetworkmaster,thedrivewilldoacoaststopratherthanrun.For
normalStart/Stopoperation,
bit0shouldbeused.
Register2:ModbusSpeedReferenceSetpoint
Thisregisterisusedtosendthespeedreferencevalue.Theinputdataisa16bitsignedintegerincludingonedecimalplace.For
example,avalueof500representsaspeedreferenceof50.0Hz,123represents12.3Hz.Itisalsopossibletoreversethedriveby
sendinganegativevaluein
thisregister.Forexample,‐1(0xFFFF)gives‐0.1Hz.‐234(0xFF16)gives‐23.4Hz.
The input value range is from‐5000 +5000; however the actual drive output frequency will be limited by the minimum and
maximumfrequenciessetinP102andP101respectively.
Register3:ModbusTorqueReferenceSetpoint
This register is used to send the torque reference / limit value when a Modbus torque reference or maximum torque limit is
selectedusingP406.Thevaluemustalwaysbepositivewitharangeof02000 =0.0200.0%ofthemotornominaltorque
capacity.
Register4:ModbusRampControlTime
Thisregisterspecifiesthedriveaccelerationanddecelerationramptimesimultaneously.Thisvaluewilloverridethevaluessetin
parametersP103andP104respectively,providingP508=1.Theinputdatarangeisfrom0to60000(0.00sto600.00s)
Readonlyregisters
Register6:Drivestatusanderrorcode
High byte : Shows thelast drive error / fault code. (Valid when the drive is tripped,a list of errorcodesis shown later in this
document)
Lowbyte:Showsthedriveoperatingstatus(0:drivestopped,1:driverunning,2:drivetipped)