APPLICATIONNOTEAN‐BEI‐P2‐038 Date:15/02/12
AN‐BEI‐P2‐038ModbusRTUControlandRegisterMapping
11
Group5:Fieldbuscommunications(Level2)
Parameter
Number
Register
Number
Description Range Scaling Type
P5‐01 501 Fieldbusdriveaddress 0…63 1=1
P5‐02 502 CANbusbaudrate
125kbps
250kbps
500kbps
1Mbps
0=125kbps
1=250kbps
P5‐03 503 Modbusbaudrate
9.6kbps,
19.2kpbs,
38.4kpbs,
57.6kpbs,
115kbps
0=9.6kbps
1=19.2kpbs
P5‐04 504 Modbusdataformat
N‐1:NoneParity1stopbit
N‐2:Noneparity2stopbits
O‐1:Oddparity1stopbit
E‐1:Evenparity1stopbit
0=N‐1
1=N‐2
P5‐05 505 Commslosstimeout 0...0.1...5.0 1=0.1s
P5‐06 506 Communicationslossaction
0:Trip
1:RamptoStopthentrip
2:Ramptostop(Notrip)
3:Presetspeed8
1=1
P5‐07 507 Fieldbusrampcontrol
0:Disable
1:Enable
1=1
P5‐08 508 Anybusmoduleoutputprocessdata4
0:Torque(%)
1:Power(x.xxkW)
2:Digitalinputstatus
3:2
nd
analoginput(%)
4.Powerstagetemperature
1=1