APPLICATIONNOTEANBEIH2038 Date:15/02/12
ANBEIH2038ModbusRTUControlandRegisterMapping
11
Group8:ApplicationSpecificParameters‐Level3
Parameter Register
Number
Description Range Scaling Type
P801 801 StirFunctionIntervalTime 0to6000
U16
P802 802 StirActivityTime 1to6000 U16
P803 803 PumpCleanFunctionConfiguration
0:Disabled
1:ActiveonStartOnly
2:ActiveonTorqueDetectionOnly
3:ActiveonStart&OverTorqueDetection
U16
P804 804 CleanTimeinterval 0to600 U16
P805 805 PumpCleanFunctionRampTime 0to60000 1=0.1s U16
P806 806 LoadProfileMonitorFunctionEnable
0:Disabled
1:LowLoadDetection
2:HighLoadDetection
3:Low&HighLoadDetection
U16
P807 807 LoadProfileMonitoringBandwidth 10to1000 10=1.0A U16
P808 808 LoadProfileMonitoringTripDelay 0to60 U16
P809 809 FireModeLogic
0:OpenActivation(NormallyClosed)
1:ClosedActivation(NormallyOpen)
U16
P810 810 FireModeSpeed 7200to7200(LimitedbyP101) 3000=50.0Hz S16
P811 811 BypassModeOnFault
0:Disabled
1:Enabled
U16
P812 812 BypassModeOnFire
0:Disabled
1:Enabled
U16
P813 813 BypassContactorChangeoverTime 0to300 1=0.1s U16
P814 814 PumpStagingFunctionSelect
0:Disabled
1:SingleDrive,FixedSpeedAssist
2:MultiDriveOptiflowControl
U16
P815 815 PumpStagingAdditionalPumps 0to4 U16
P816 816 PumpStagingDutySwitchoverTime 0to1000 U16
P817 817 PumpStagingDOLSwitchinspeed 0to7200(LimitedbyP101) 3000=50.0Hz U16
P818 818 PumpStagingDOLSwitchoutspeed 0to7200(LimitedbyP101) 3000=50.0Hz U16
P819 819 PumpStagingSystemSettleTime 10to600 U16
P820 820 PumpStagingMasterClockReset
0:NoFunction
1:ResetTimer
U16
