APPLICATIONNOTEAN‐BEI‐H2‐038 Date:15/02/12
AN‐BEI‐H2‐038ModbusRTUControlandRegisterMapping
11
Group8:ApplicationSpecificParameters‐Level3
Parameter Register
Number
Description Range Scaling Type
P8‐01 801 StirFunctionIntervalTime 0to6000
U16
P8‐02 802 StirActivityTime 1to6000 U16
P8‐03 803 PumpCleanFunctionConfiguration
0:Disabled
1:ActiveonStartOnly
2:ActiveonTorqueDetectionOnly
3:ActiveonStart&OverTorqueDetection
U16
P8‐04 804 CleanTimeinterval 0to600 U16
P8‐05 805 PumpCleanFunctionRampTime 0to60000 1=0.1s U16
P8‐06 806 LoadProfileMonitorFunctionEnable
0:Disabled
1:LowLoadDetection
2:HighLoadDetection
3:Low&HighLoadDetection
U16
P8‐07 807 LoadProfileMonitoringBandwidth 10to1000 10=1.0A U16
P8‐08 808 LoadProfileMonitoringTripDelay 0to60 U16
P8‐09 809 FireModeLogic
0:OpenActivation(NormallyClosed)
1:ClosedActivation(NormallyOpen)
U16
P8‐10 810 FireModeSpeed ‐7200to7200(LimitedbyP1‐01) 3000=50.0Hz S16
P8‐11 811 BypassModeOnFault
0:Disabled
1:Enabled
U16
P8‐12 812 BypassModeOnFire
0:Disabled
1:Enabled
U16
P8‐13 813 BypassContactorChangeoverTime 0to300 1=0.1s U16
P8‐14 814 PumpStagingFunctionSelect
0:Disabled
1:SingleDrive,FixedSpeedAssist
2:MultiDriveOptiflowControl
U16
P8‐15 815 PumpStagingAdditionalPumps 0to4 U16
P8‐16 816 PumpStagingDutySwitchoverTime 0to1000 U16
P8‐17 817 PumpStagingDOLSwitchinspeed 0to7200(LimitedbyP1‐01) 3000=50.0Hz U16
P8‐18 818 PumpStagingDOLSwitchoutspeed 0to7200(LimitedbyP1‐01) 3000=50.0Hz U16
P8‐19 819 PumpStagingSystemSettleTime 10to600 U16
P8‐20 820 PumpStagingMasterClockReset
0:NoFunction
1:ResetTimer
U16