APPLICATIONNOTEAN‐BEI‐H2‐038 Date:15/02/12
AN‐BEI‐H2‐038ModbusRTUControlandRegisterMapping
10
Group6:AdvancedParameterset(Level3)
Par Register Description Range Scaling Type
P6‐01 601 FirmwareUpgradeenable
0:Disabled
1:Enable(IOandDSP)
2:Enable(IOonly)
3:Enable(DSPonly)
U16
P6‐02 602 Autothermalmanagement
0:Disable
1:Enable
U16
P6‐03 603 Auto‐resetdelaytime 1to60 U16
P6‐04 604 Userrelayhysteresisband 0‐ 250 1=0.1% U16
P6‐08 608 Maxspeedreffrequency 0,5 to20 U16
P6‐10 610 EnablePLCoperation
0:Disable
1:Enable
U16
P6‐11 611 Speedholdtimeonenable 0to2500 1=0.1s U16
P6‐12 612 Speedholdtimeondisable 0 to2500 1=0.1s U16
P6‐18 618 DCinjectionbrakingvoltage
0:Auto
0to250
0=Auto
1=0.1%
U16
P6‐22 622 Resetcoolingfanrun‐time
0:Disable
1:Enable
U16
P6‐23 623 ResetkWhmeter
0:Disable
1:Enable
U16
P6‐24 624 Servicetimeinterval
0…60000h
(0=disabled)
1=1
U16
P6‐25 625 Resetserviceindicator
0:Disable
1:Reset
1=1
U16
P6‐26 626 Analogoutput1scaling 0to5000 1=0.1 U16
P6‐27 627 Analogoutput1offset‐5000to5000 1=0.1% S16
P6‐28 628 P0‐80displayvalueindex 0to127 U16
P6‐29 629 SaveUserParametersasdefault
0:Disable
1:Enable
U16
P6‐30 630 Level3accesscode 0to9999 U16
Group7:MotorControlParameterset(Level3)
Parameter Register
Number
Description Range Scaling Type
P7‐01 701 MotorStatorresistance Drivedependent 1=0.001ohm U16
P7‐04 704 MotorMagnetisingCurrent Drivedependent 1=0.1A U16
P7‐11 711 Pulsewidthminimumlimit 0 to500 (Time= value*16.67ns) 1=1 U16
P7‐12 712 V/Fmodemagnetisingperiod 0to2000 U16
Comentarios a estos manuales