TxA Maintenance
3 TxA Maintenance
3.1 Software
Maintenance of the TxA is similar to maintenance of the other iX Panel, with a few
important differences, described in this document.
It is possible to update the TxA wit h new system software and to make service
settings such as touch calibration, IP settings, self t est etc. These acti ons are
performed by following the procedures des cribed below.
3.1.1 Entering Update Mode
In order to update the system software of the iX Panel, you first have to download
the new image from the Beijer Electronics website to your PC.
Follow the steps below:
• Hold a finger anywhere on the touch screen when applying power to the
panel. After a few seconds the following message is displayed:
– Enter update mode?
– Release touch.
• Release the finger from the screen. The following message is displayed:
– Touch screen to enter update m ode
• Touch the screen once with a finger to enter the update mode. Otherwise the
panelwillstartinnormalmodeafter5seconds.
Now the update screen is shown and the panel is ready for image update, according
to the instructions on the screen.
Detailed information about the upgrade procedure is available in the iX Developer
help file, in the Operator Panel Upgrade chapter.
3.1.2 Entering the Service Menu
Perform the following steps to enter the service menu:
• Apply power to the panel
• When the hourglass sy mbol disappears, press a finger on the screen and hold
until the touch calibration screen displays the following message:
– Tap anywhere on screen or touch calibrate will start in 10 seconds.
• Lift the finger and press onc
e again to enter the service menu
Beijer Electronics, MAEN021
9
Comentarios a estos manuales