Beijer-electronics iX Panel TA70 EN Manual de usuario Pagina 17

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 23
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 16
Additional Installation Tips
6.2 EthernetConnectioninthePanel
1
2
3
4
5
1-1
2-2
3-3
8-8
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
RJ45
Industrial Ethernet
Operator panel
Operator panel
Operator panel
Operator panel
Shielded
Short and
unshielded
0.1 uF
250 V
5351
In some industrial units for Et hernet, the RJ45 contacts shield is connected to the
chassis via a capacitor, see 1 in drawing above.
The operator panels Ethernet shield is directly
connected to the chassis, see 2 in
drawing above.
1.
Check whether the other Ethernet unit has its shield directly grounded or
grounded via a capacitor.
Note:
Inmanycases,connectingtheshieldedEthernetcablingtothechassisatbothendsis
inappropriate. Humorgroundingloopscanoccur. Unshieldedcablingmayevenresult
infewercommunicationerrors.
A good solution may be to use a shielded Ethernet cable, but to connect the shield
at one end only.
One option is to break the shield, see 3 in drawing above.
A more elegant method is to expand th e shi elded Ethernet cabling with a piece of
unshielded Ethernet cable, see 4 in drawing above.
You can ground the shield via an external 0.1 uF/250 V plastic capacitor, see 5 in
drawing above. Thi s will connect the HF transients to the ground.
BeijerElectronics, MAEN009A
17
Vista de pagina 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 23

Comentarios a estos manuales

Sin comentarios